NFPA 1403 Fire Simulator Structural Evaluation Requirements


NFPA 1403 and F.A.C. 69
Fire Simulator
Structural Evaluation Requirements

 

69A-37.404 Requirements for Live Fire Training

States in part “(18)(a) The 2002 edition of the National Fire Protection Association, Inc., Publication 1403, "Standard on Live Fire Training Evolutions," is hereby adopted and incorporated by reference…”

 

NFPA 1403-2002 requires


5.2.2.2 The structural integrity of the building shall be evaluated and documented annually by a licensed professional engineer with burn building experience and expertise.

5.2.2.3 Part of the burn building evaluation shall include, once every five years, the removal and reinstallation of a representative area of thermal linings (if any) to inspect the hidden conditions behind the linings.

5.2.2.4 The engineer shall core solid structural concrete slabs and walls that have been exposed to temperatures in excess of 149°C (300°F) to check for hidden delamination and to test comprehensive strength once every 10 years for conventional (Portland) concrete and every three years for refractory (calcium aluminate) concrete.

5.2.2.5 Where the burn building damage is severe enough to affect the safety of the students, training shall not be permitted.

Are you in compliance?

For more information contact Byron Evetts, P.E, Fire Fighter, USAR Structures Specialist and NAFI Fire Investigator.

“Our goal is to keep you training, safely.”

 

Contact:

See Contact page or call the office at 321.784.5811 or E-mail us here.






 

Slideshow, please click on first image and use the "Next" or "Previous" buttons on the upper right or left hand side of each full size image as your mouse approaches that area of each image. The "Close" slideshow is at the bottom of each image in case you are on a laptop and cannot see the close button.